Non IBR Boilers

Oil Fired Steam Boilers, IBR Boilers, Steam Generating Boilers, Non- IBR Boilers, Baby Boilers, India

Non-IBR Boilers

Revotech : Non IBR four pass fully steam generating boiler in oil fired design

Salient Features :
1) Fully automatic instant steaming.
2) Easy operation fail proof system.
3) Record efficiency.
4) Packaged models in unitised design.
REVOTECH is the latest design in coil type Non - IBR boilers. incorporating unique revolutionary principle of combustion known as " Reverse Flow " which increases combustion efficiency & allows high rate of heat flux & increases the efficiency of whole system. The boiler is also comprising of an atmospheric economizer to preheat the incoming feed water to boiler.

As REVOTECH is a fully automatic boiler there is no need of specially trained boiler attendant during operation.

NON – 1BR : The volumetric holding of the steam generating coil is less than 25 litres, by virtue of which the boiler is exempted from Indian Boiler Regulations.

Forced circulation, water tube & Reverse flow design enables the boiler to produce steam at full working within 3 to 5 minutes from cold start.

REVOTECH is fully safe as it is having all safety precautions. REVOTECH is available in a wide range of steam generating capacities from 50 Kgs/hr to 1000 Kgs/hr F & A 100°C designed for maximum pressure of 15 Kg/cm2 at overall efficiency of 88± 2% on N . C . V.

 
P & I DIAGRAM OF AN OIL FIRED STEAM BOILER - REVOTECH
 
Technical Specifications :
Details Unit RT-03 RT-04 RT-05 RT-06 RT-08 RT-10
OPERATING PARAMETERS
Steam output F & A 100oC. Kgs/hr 300 400 500 600 800 1000
Steam pressure Kgs/cm2 15 15 15 15 15 15
Fuel Oil Consumption LDO
FO

Kgs/hr
Kgs/hr

18
19.1

24
25.4

30
31.8

36
38.1

48
50.8

60
63.6
Efficiency (NCV) % -------------> 88 + 2 <-------------------------
Start up Minutes 3 3 5 5 5 5
Burner control ----------------------> ON/OFF <---------------------------------
Pressure parts OUTSIDE THE PURVIEW OF INDIAN BOILER REGULATIONS
Electric Supply AC - 3 - PHASE : 415 V - 6% ; 50 Hz = 3%; 4 wire
Connected Electrical Load  
Feed water pump water HP 1 1 1 1 1.5 1.5
Blower HP 1 1 1.5 1.5 3 5
Fuel Pump Motor HP 0.5 0.5 0.5 0.5 0.5 0.5
(For F O fired units only)

Total electrical load for :

LDO Fired Units
FO Fired Units
KW 3





2.5 HP
2.5 HP+3KW
4.5





2.5 HP
2.5 


6





3 HP

6





3 HP
3HP + 6
7.5





5 HP
5
7.5





7 HP + 7.5 KW
      HP+4.5 KW HP+6 KW KW HP+7.5 KW  
Flue Gas outlet mm 200 200 200 250 300 300
Dry Weight (approx.) Kgs 1300 1400 1600 1700 1800 1950
Nanomatic Minimatic
 
 
 
 
 
Burners : Light Oil Burners    :-   One Stage Oil Burner   |   Two Stage Oil Burner    |   Three Stage Operation    |   
                                     Two Stage Progressive or Modulating Oil Burners    |    Single Stage and Two Stage
    Gas Oil Burners      :-    Low Nox One & Two Stage Gas Burner    |   Progressive Two Stage Modulating Gas Burners
    Heavy Oil Burners  :-    Two Stage Operatiion    |   Three Stage Heavy Oil or Modulating
    Dual Fuel Burners   :-    Gas / Light Oil Burner   |   Gas / Heavy Oil Burner
Boilers : Non-IBR Boilers    |   Nanomatic Boilers   |   Mini Steam Generators
Thermic Fluid Heaters    |   Hot Air Generators    |    Hot Water Generators    |    Tank Heating Systems    |    
Water Softner
   |    Ovens
 
Home    |   Profile    |   Products      Infrastructure    |   Our Agents    |   Contact    |   Enquiry
Designed & Hosted by : MID   Promoted by : GID